Advertisement
Advertisement
INTERSCHUTZ 2020, 15 - 20 June, Hannover/Germany
Homepage>Exhibitors & Products >Helium leak test machine

Helium leak test machine

Leak test of portable fire extinguishers from 1 kg to 12 kg

Logo Helium leak test machine
Logo Helium leak test machine
Logo Helium leak test machine
Logo Helium leak test machine

Product description

for leak test of portable fire extinguishers from 1 kg to 12 kg
in accordance with European standard EN3-7. ( 6% of the expanded gas per year )

Model HLT02
Leak test of extinguisher for example by a 6 kg stored pressure extinguisher:
- Nitrogen volume = 3,666666 litre by 16 bar
- Expanded Nitrogen volume = 58,66666 barlitre
- Tolerated leak per year = 3,52 barlitre
- Tolerated leak per second =0,0000001116 barlitre = 1,12E-7 barl/sec = 1,12E-4 mbarl/sec
- By using of 10% Helium in the nitrogen the equipment will be able to measure this fine leak rate
of 0,00001116 mbarl/sec = 1,12E-5 mbarl/sec = ccm/sec in one minute.